Sample Group
Lead and Copper water quality parameters
Sample ID
1708C06-001B
Source ID
8
Well #
BF508
Sample Date
8/14/2017
Sample Time
1050
Site ID
UW8
Sample Description
Sample Type
Compliance
Reported Date
8/24/2017
Sample Source
Entry Point
# Taken
1
Sample Collector
T BLOCK
Lab ID
399089350
Lab Name
Metiri - Geneva
Reason for No Results
Lab Comment

Sampling Results

Storet Code Description Result Units Qualifier MCL MCL Units Limit of Quantitation Limit of Detection Labslip Order
1927 ALKALINITY,TOTAL 322 MG/L MG/L 20 20 1
1017 CHLORIDE 21 MG/L Between LOD and LOQ MG/L 30 20 2
1012 CHLORINE TOTAL RESIDUAL 0.93 MG/L MG/L 3
1013 CHLORINE FREE (AVAILABLE) 0.49 MG/L MG/L 4
1064 CONDUCTIVITY @ 25 C U-MHO 619 UMHOS/CM UMHO/CM 1 1 5
1925 PH 7.25 SU SU 6
1055 SULFATE 17.8 MG/L MG/L 5.1 1.702 7
1996 TEMPERATURE (CENTIGRADE) 12.1 C C 8