Sample Group
Lead and Copper water quality parameters
Sample ID
1197560
Source ID
29
Well #
RG653
Sample Date
7/7/2020
Sample Time
900
Site ID
UW29EP
Sample Description
Sample Type
Compliance
Reported Date
7/15/2020
Sample Source
Entry Point
# Taken
1
Sample Collector
K MILLER
Lab ID
721026460
Lab Name
Northern Lake Service Inc. (Crandon)
Reason for No Results
Lab Comment

Sampling Results

Storet Code Description Result Units Qualifier MCL MCL Units Limit of Quantitation Limit of Detection Labslip Order
1927 ALKALINITY,TOTAL 310 MG/L MG/L 4.0 2.0 1
1002 ALUMINUM 0 MG/L Non-detect MG/L 0.079 0.024 2
1016 CALCIUM 71 MG/L MG/L 0.12 0.035 3
1017 CHLORIDE 7.3 MG/L MG/L 5.0 0.46 4
1012 CHLORINE TOTAL RESIDUAL 0.43 MG/L Field Result MG/L 5
1013 CHLORINE FREE (AVAILABLE) 0.37 MG/L Field Result MG/L 6
1064 CONDUCTIVITY @ 25 C U-MHO 614 UMHOS/CM UMHO/CM 7
1915 HARDNESS, TOTAL (CAC03) 340 MG/L MG/L 0.54 0.16 8
1028 IRON 0.016 MG/L Between LOD and LOQ MG/L 0.025 0.0070 9
1032 MANGANESE 0 UG/L Non-detect MG/L 6.7 2.0 10
1925 PH 7.37 SU Field Result SU 11
1055 SULFATE 10 MG/L MG/L 5.0 1.5 12
1996 TEMPERATURE (CENTIGRADE) 10.6 C Field Result C 13