Sample Group
Lead and Copper water quality parameters
Sample ID
1198321
Source ID
16
Well #
BF516
Sample Date
7/8/2020
Sample Time
639
Site ID
UW16EP
Sample Description
Sample Type
Compliance
Reported Date
7/20/2020
Sample Source
Entry Point
# Taken
1
Sample Collector
J ALLAN
Lab ID
721026460
Lab Name
Northern Lake Service Inc. (Crandon)
Reason for No Results
Lab Comment

Sampling Results

Storet Code Description Result Units Qualifier MCL MCL Units Limit of Quantitation Limit of Detection Labslip Order
1927 ALKALINITY,TOTAL 270 MG/L MG/L 4.0 2.0 1
1002 ALUMINUM 0 MG/L Non-detect MG/L 0.079 0.024 2
1016 CALCIUM 73 MG/L MG/L 0.12 0.035 3
1017 CHLORIDE 78 MG/L MG/L 5.8 1.7 4
1012 CHLORINE TOTAL RESIDUAL 0.45 MG/L Field Result MG/L 5
1013 CHLORINE FREE (AVAILABLE) 0.4 MG/L Field Result MG/L 6
1064 CONDUCTIVITY @ 25 C U-MHO 843 UMHOS/CM UMHO/CM 7
1915 HARDNESS, TOTAL (CAC03) 360 MG/L MG/L 0.54 0.16 8
1028 IRON 0.0074 MG/L Between LOD and LOQ MG/L 0.025 0.0070 9
1032 MANGANESE 0 UG/L Non-detect MG/L 6.7 2.0 10
1925 PH 7.31 SU Field Result SU 11
1055 SULFATE 13 MG/L MG/L 5.0 1.4 12
1996 TEMPERATURE (CENTIGRADE) 11.5 C Field Result C 13