Description
There is not at least one adequately sized well vent installed through the well pump casing, well seal, or concrete pump base which terminates at least 24" above the floor in reverse bend (or mushroom style cap) with a 24-mesh screen.
Compliance Due
8/18/2017
Compliance Achieved
6/29/2017
Identified On
6/28/2017 Sanitary Survey
Category
Pumps/Pump Facilities and Controls
Code Citation
811.36(1)
Actions Taken
Severity
Deficiency