Description
Overflows of elevated storages are not provided with a sufficient 4 mesh non corrodible screen and/or ground level overflows are not provided with a sufficient 24 mesh noncorrodible screen.
Compliance Due
8/31/2020
Compliance Achieved
8/10/2020
Identified On
7/21/2020 Sanitary Survey
Category
Finished Water Storage
Code Citation
811.64(4)
Actions Taken
Severity
Deficiency